Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. ___ Resolve the red tag attached to the fryer extinguishing system ___ Recap all nozzles above appliances. ___ Clear area around pull stations. |
|
| 01/13/2009 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. |