Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

01/13/2009

Applicant:

JOHNSON D & B FAMILY LLC

Description:

Burger king full fire inspection.

Outstanding Inspections

Case Number: T09FR00209
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
01/13/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels
01/13/2009 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
01/13/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. ___ Resolve the red tag attached to the fryer extinguishing system ___ Recap all nozzles above appliances. ___ Clear area around pull stations.
01/13/2009 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
01/13/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
01/13/2009 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR00209
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/13/2009 INSP - FULL JLOYA Approved
02/04/2009 INSP - REINSPECTION JLOYA Approved