Case: T09FR00018

Parcel: 121082950


Addresses:

6206 E PIMA ST


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR00018

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/05/2009 INSP - FULL Correction Required DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE PROVIDED THE FIRE PREVENTION OFFICE

1) PROVIDE SIGNAGE FOR THE INSPECTORS TEST AND MAIN DRAIN

2) PROVIDE A LOCK AND CHAIN FOR THE MAIN CONTROL VALVE

3) SUITE # 4 - WATER HEATER CLOSET - A CEILING HAS NOT BEEN INSTALLED IN THIS ROOM. A HEAT COLLECTION DEVICE SHALL BE PROVIDED OR THE SPRINKLER SHALL BE RAISED TO THE CORRECT POSITION