Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CHECKED PERMIT HISTORY FOR THIS ADDRESS, THERE IS NO PERMIT HISTORY FOR SERVICE UPGRADE. NEED TO OBTAIN PERMIT FOR SERVICE UPGRADE ALONG WITH THIS RECONNECT PERMIT 2) INSTALL SMOKE DETECTORS IN BEDROOMS PER INSTRUCTIONS 3) VERIFY GROUNDED RECEPTS, HAVE EQUIPMENT GROUND OR NEED TO BE GFI PROTECTED 4) INSTALL BREAKERS LISTED FOR USE IN SIEMENS PANEL 5) RESCHEDULE WHEN COMPLETE |
|
| 01/13/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) UNIT LOCKED 2) NO ACCESS-NEED ACCESS TO INTERIOR 3) WERE SERVICE CONDUCTORS REPLACED ? |