Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09EL01969
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/01/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) GROUND CONNECTIONS IN PLUG MOLD NEED A TERMINAL END AND NOT A SHEET METAL THREAD SCREW 2) OK ELECTRIC AFTER CORRECTIONS |
|
09/29/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ISOLATED GROUND CIRCUITS REQUIRE ISOLATED GROUND FOR GROUND TERMINAL ON RECEPT AND EQUIPMENT GROUND FOR BOX AND RACEWAYS 2) EQUIPMENT GROUNDS FOR 30 AMP CIRCUITS TO BE #10 NEC 250.122 3) NEED UPDATED PANEL DIRECTORY 4) HAVE PANEL OPEN FOR NEXT INSPECTION 5) FINISH WORK |