Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09EL01969

Parcel: 117200250


Addresses:

270 S STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09EL01969

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/01/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) GROUND CONNECTIONS IN PLUG MOLD NEED A TERMINAL END AND NOT A SHEET METAL THREAD SCREW
2) OK ELECTRIC AFTER CORRECTIONS
09/29/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ISOLATED GROUND CIRCUITS REQUIRE ISOLATED GROUND FOR GROUND TERMINAL ON RECEPT AND EQUIPMENT GROUND FOR BOX AND RACEWAYS
2) EQUIPMENT GROUNDS FOR 30 AMP CIRCUITS TO BE #10 NEC 250.122
3) NEED UPDATED PANEL DIRECTORY
4) HAVE PANEL OPEN FOR NEXT INSPECTION
5) FINISH WORK