Permit: T09EL01967

Parcel: 10612016A

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09EL01967

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
10/21/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
09/29/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REINSPECTION FEE NEXT INSPECTION IF NO COMPLIANCE
2) SEE NOTES INSPECTION 9/02/09 #2 ALSO BE SURE TO SUPPORT TO STRUCTURE (CABLE)
3) PROVIDE PERMIT CARD
4) UNIT MUST HAVE HEATING AND COOLING TO BE CONSIDERED HABITABLE-SEE HAND OUT
5) COVERS MISSING
09/16/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
Recall inspection - have elect on site to remove covers to outlets & power.
09/02/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RECEPT AT PEDESTAL BOX WAS CONVERTED FROM 240V TO 120V, WIRE RECEPT, WITH HOT, NEUTRAL, GROUND, IDENTIFY CONDUCTORS ACCORDINGLY
2) ROMEX TO HAVE APPROVED CLAMP TYPE CONNECTORS AT TERMINATIONS INTO PANEL
08/27/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL SMOKE DETECTORS IN SLEEPING AREAS
2) WIRING EXPOSED IN SOME AREAS
3) PROVIDE GFI PROTECTION FOR BATHROOM RECEPT
4) CLAMP LIFE LINE TO BREAKER BOX
5) USE PROPER SIZED CIRCUIT BREAKERS:
10 GA=30 AMP BKR OR LESS
12 GA=20 AMP BKR OR LESS
14 GA=15 AMP BKR OR LESS
6) 1P 30 AMP CIRCUIT BREAKER TO FEED 120V 30 AMP RV RECEPT