Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T09DV00208

Parcel: 118120550


Addresses:

216 E 22ND ST

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
01/17/2009 INSP - INITIAL CODE ENFORCMENT Approved MAIN SERVICE PANEL HAS BE TAMPERED WITH, 3 CIRCUITS BREAKERS HAVE BEEN DOUBLE LUGGED. 3 FEEDERS TO RECEPTACLE BOXES EXTERIOR OF MAIN DISCONNECT ARE PROVIDING POWER TO OTHER RECEPTACLE BOXES AND ONE 220 AMP COMPRESSOR WHICH IS HARD WIRED TO THE UNIT. THE INTERIOR OF THE DWELLING HAS RECEPTACLES IN BOTH BEDROOMS AND BATH ROOMS THAT ARE INOPERABLE, SAME WITH LIGHTS IN THESE AREAS. THE KITCHEN AND LIVING ROOM ARE OPERABLE. THE JUNCTION BOX UNDER PORCH AREA HAS CONDUCTORS DISCONNECTED WHICH LEAD INTO THE INTERIOR OF THE DWELLING.
EXTENSION CORDS WERE FOUND IN THE INTERIOR AND EXTERIOR OF THE PROPERTY. ACTION TAKEN WAS THE 3 RECEPTACLE BOXES UNDER THE DISCONNECT HAD THE EXTENSION CORD REMOVED AND THE 3 CIRCUIT BREAKERS WERE SHUT OFF. THE OWNER WAS PRESENT AT THE DISCONNECT AND WAS GIVEN AN NOTICE OF VIOLATION TO HAVE THE EXPOSED, DISCONNECT WIRING UNDER THE PORCH CORRECTED. THE ORDER ALSO STATED TO REMOVE THE ADDED CONNECTIONS (THE DOUBLE LUGGING REMOVED.) ALL WORK MUST BE PERMITTED AND DONE BY A LICENSED CONTRACTOR WITHIN 10 DAYS.

JUNCTION BOX UNDER PROCH AREA HAS CONDUCTORS DISCONNECTED INTERIOR OF DWELLI