Permit: T09CM03203

Parcel: 120090510


Addresses:

4407 S 6TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
03/29/2010 MECHANICAL - HOODS Approved IVRS - Inspection :*
03/15/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) COMPLETE CAULKING ON HOOD
2) COMPLETE FIRE SUPRESSION SYSTEM
3) GAS FLEXES NOT TO EXCEED 36"
4) VENT PIPE ON ROOF TO BE 3' ABOVE COOLER
5) SEAL ALL HOLES IN EXTERIOR OF HOOD
6) PROVIDE COVER OVER BACK OF STOVE (ELECTRICAL)
03/12/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) PROVIDE A QUICK DISCONNECT GAS CONNECTOR AND A LANYARD FOR STOVE ON WHEELS
2) FINISH WIRING 1 EXHAUST FAN
3) INSTALL GASKETS UNDER FANS
4) FINISH MAKE UP AIR LOUVERS
5) PROVIDE GREASE RECEPTORS AT FANS
01/12/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
01/11/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) WALL FLASHING TO EXTEND 18" BEYOND HOOD
12/31/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED FIRE WRAP, OK TO INSTALL HOODS
12/29/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) OK FOR SECOND LAYER BOTH DUCTS
12/28/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) OK SMOKE LEAK TEST BOTH HOODS, OK FOR WRAP
12/17/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON GREASE DUCT-OK FOR 1ST LAYER FIRE WRAP
12/09/2009 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) PROCEED WITH DUCT AS DISCUSSED