Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2010 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 03/15/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) COMPLETE CAULKING ON HOOD 2) COMPLETE FIRE SUPRESSION SYSTEM 3) GAS FLEXES NOT TO EXCEED 36" 4) VENT PIPE ON ROOF TO BE 3' ABOVE COOLER 5) SEAL ALL HOLES IN EXTERIOR OF HOOD 6) PROVIDE COVER OVER BACK OF STOVE (ELECTRICAL) |
|
| 03/12/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PROVIDE A QUICK DISCONNECT GAS CONNECTOR AND A LANYARD FOR STOVE ON WHEELS 2) FINISH WIRING 1 EXHAUST FAN 3) INSTALL GASKETS UNDER FANS 4) FINISH MAKE UP AIR LOUVERS 5) PROVIDE GREASE RECEPTORS AT FANS |
|
| 01/12/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
| 01/11/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) WALL FLASHING TO EXTEND 18" BEYOND HOOD |
|
| 12/31/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED FIRE WRAP, OK TO INSTALL HOODS |
|
| 12/29/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) OK FOR SECOND LAYER BOTH DUCTS |
|
| 12/28/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) OK SMOKE LEAK TEST BOTH HOODS, OK FOR WRAP |
|
| 12/17/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) CHECKED WELDS ON GREASE DUCT-OK FOR 1ST LAYER FIRE WRAP |
|
| 12/09/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PROCEED WITH DUCT AS DISCUSSED |