Permit: T09CM03201

Parcel: 12218234A

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/01/2010 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
AS BUILT ON SITE
OK TO COVER
01/29/2010 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE ISOMETRIC DETAIL FOR RESTROOMS #106 & 107-INCLUDE P.O.C. TO EXISTING, ALL EXISTING PIPING, ALL NEW PIPING AND CONNECTIONS TO 2ND FLOOR
2) HORIZONTAL VENTING BELOW THE FLOORD RIM LIMITED TO STRUCTURAL CONDITION
3) VENT FITTINGS BELOW THE FLOOD RIM TO BE DRAINAGE TYPE
4) STAND PIPE RECEPTORS TO BE ROUGHED IN ABOVE GRADE
5) ALL DRAINAGE PIPING TO HAVE 8 PERCENT GRADE
6) CAP OFF AL DEMO'D PIPING IN AND APPROVED MANNER