Permit: T09CM03118

Parcel: 110111310


Addresses:

4917 E BERMUDA ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/29/2010 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/19/2010 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THERE IS A SLIGHT LEAK AT HEAT EXCHANGER CONNECTION TO WATER HEATER DRAIN
2) ALSO YOUR APPROVED PLAN DOE NOT SHOW THIS HEAT EXCHANGER ASSEMBLY, BUT RATHER INDICATES A SOLAR STORAGE TANK WITH SEPERATE CONNECTIONS FOR HEAT EXCHANGER
3) PROVIDE A DETAIL FOR FAFCO PANELS ON A FLAT ROOF
4) MORE SUPPORTS ARE NEEDED TO KEEP TUBING OFF ROOF
5) ALSO DIAGRAM PROVIDED IS MISSING KEY CHART EXPLAINING WHAT EACH SYMBOL REPRESENTS
6) IS SYSTEM PUMPED ?
12/11/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A PERMIT FOR NEW ELECTRICAL WIRING
2) PROVIDE A CITY APPROVED PLAN WITH PIPING DIAGRAM FOR INSTALLATION
3) BRASS OR DIELECTRIC PROTECTION AT WATER HEATER DRAIN CONNECTION
4) MIXING VALVE REQUIRED
5) PIPING NOT SOLDERED AT T & P VALVE
6) SOLAR PANEL AND ALL PIPING SHALL BE SUPPORTED WITH CLEARANCE ABOVE FLAT ROOF, WHERE NAILS HAVE BEEN DRIVEN INTO ROOFING, THE ROOF SHALL BE PROPERLY PATCHED