Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/21/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT PANEL AND ROOF TOP PIPING MINIMUM 1 1/2" ABOVE ROOF SURFACE 2) PROVIDE UV LISTED ROOF TOP PIPING 3) INSULATION TO BE SEALED PROPERLY WITH NO GAPS AND HAVE UV PROTECTION FROM SUNLIGHT 4) PROPERLY REPAIR HOLES IN ROOF FROM SUPPORTS DIRECTLY THRU ROOF SURFACE WITHOUT ANY FORM OF WEATHER PROOF |