Inspection Status: Denied
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TERMINATE CONDENSATE TO AN APPROVED LOCATION 2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE 3) PROVIDE A TRAP ON CONDENSATE DRAIN 4) PROVIDE A SECONDARY OVERFLOW SENSOR 5) INSULATE ALL METAL DUCTING ABOVE FURNACE 6) PROVIDE A VENT FOR FURNACE AND WATER HEATER 7) DO NOT HAVE PVC WITHIN 6" OF SINGLE WALL VENT 8) GAS FLEX CONNECTOR CANNOT PASS THRU THE CABINET OF FURNACE 9) PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE 10) PROVIDE PROTECTION ON REFER LINES AT CONNECTION TO EVAP COIL 11) PROVIDE A ROMEX CONNECTOR AT FURNACE CORD 12) CORRECTIONS ARE TOO NUMEROUS TO LIST 13) HAVE MECHANICAL CONTRACTOR ON JOB SITE AT NEXT INSPECTION 14) DO NOT USE MC CABLE EXPOSED ON ROOF 15) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS 16) LIST MAY NOT BE COMPLETE |