Permit: T09CM03052

Parcel: 136251190


Addresses:

6609 E MARY DR

Inspection Status: Denied

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
11/20/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TERMINATE CONDENSATE TO AN APPROVED LOCATION
2) USE PURPLE PRIMER ON ALL PVC FITTINGS PRIOR TO GLUE
3) PROVIDE A TRAP ON CONDENSATE DRAIN
4) PROVIDE A SECONDARY OVERFLOW SENSOR
5) INSULATE ALL METAL DUCTING ABOVE FURNACE
6) PROVIDE A VENT FOR FURNACE AND WATER HEATER
7) DO NOT HAVE PVC WITHIN 6" OF SINGLE WALL VENT
8) GAS FLEX CONNECTOR CANNOT PASS THRU THE CABINET OF FURNACE
9) PROVIDE A SEDIMENT TRAP IN GAS LINE TO FURNACE
10) PROVIDE PROTECTION ON REFER LINES AT CONNECTION TO EVAP COIL
11) PROVIDE A ROMEX CONNECTOR AT FURNACE CORD
12) CORRECTIONS ARE TOO NUMEROUS TO LIST
13) HAVE MECHANICAL CONTRACTOR ON JOB SITE AT NEXT INSPECTION
14) DO NOT USE MC CABLE EXPOSED ON ROOF
15) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS
16) LIST MAY NOT BE COMPLETE