Permit: T09CM02811

Parcel: 11451216G

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09CM02811

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/30/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AUDIBLE ALARMS FOR DUCT SMOKE DETECTORS
2) AIR BALANCE IS OK
3) BATHROOM EXHAUST NEEDS TO BE ON A TIME CLOCK
4) TERMINATE CONDENSATE TO AN APPROVED LOCATION
5) PERMANENTLY I.D. A/C UNITS
6) MARK DATA PLATE AND FUSE ACCORDINGLY
7) STEP UP CONDENSATE TO 1" AT 1ST TEE