Permit: T09CM02532

Parcel: 11706183B

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T09CM02532

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/28/2010 BUILDING - FINAL Approved IVRS - Inspection :*
1) OK FOR C OF O
01/20/2010 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) FIRE STOP OK
2) NEED TRADE FINALS
12/16/2009 BUILDING - FINAL Not ready for Inspection REVISE PLANS TO DELETE MECHANICAL TO CORRIDOR; TO DELETE "MINI-SPLIT" IN FUTURE TENANT SPACE; TO MODIFY OCCUPANT LOAD (DOES NOT COMPLY WITH CH. 29 IBC); TO DELETE THE DOORS SHOWN ON THE M, P, E PAGES; TO ADDRESS THE FUTURE TENANT BEING FED ELECTRICALLY THROUGH THIS TENANTS SUB PANEL; AND TO DELET ALL THE ELECTRICAL FIXTURES IN THE FUTURE TENANT SPACE.