Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02434
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC 2) RECEIVED GENERATOR REPORT |
|
06/09/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE PROVIDE COPY OF LATEST GENERATOR TEST REPORT TO VERIFY WORKING CONDITIONS 2) PANEL DIRECTORIES TO BE PER 408.4 3) OUTDOOR RECEPT COVER TO BE PER 406.8 4) CLEAN SURFACE UNDERGROUND LUG DISCONNECT ELEVATOR ROOM 5) BOND LIGHT POLES TO CIRCUIT 250.53 6) SPLICES TO BE FOR WET LOCATIONS IN PARKING LOT PULL BOX 7) FINISH FLOOR BOXES |
|
06/07/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |