Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T09CM02434

Parcel: 117200270


Addresses:

260 S CHURCH AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM02434

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ELECTRIC
2) RECEIVED GENERATOR REPORT
06/09/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) PLEASE PROVIDE COPY OF LATEST GENERATOR TEST REPORT TO VERIFY WORKING CONDITIONS
2) PANEL DIRECTORIES TO BE PER 408.4
3) OUTDOOR RECEPT COVER TO BE PER 406.8
4) CLEAN SURFACE UNDERGROUND LUG DISCONNECT ELEVATOR ROOM
5) BOND LIGHT POLES TO CIRCUIT 250.53
6) SPLICES TO BE FOR WET LOCATIONS IN PARKING LOT PULL BOX
7) FINISH FLOOR BOXES
06/07/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*