Permit: T09CM02334

Parcel: 130180020


Addresses:

4100 E 29TH ST #05


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM02334

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/07/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/06/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) COMPLETE PREVIOUS INSPECTION ITEMS
2) REPLACE BOXES AS REQUIRED TO ALLOW PROPER WIRE FILL AND DEVICES TO BE INSTALLED
10/05/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROPERLY SPLICE EQUIPMENT GROUNDS
2) BOND EQUIPMENT GROUNDS TO METAL BOXES
3) REPLACE DAMAGED CABLES FROM FIRE
4) REMOVE FIRE DAMAGED LIGHT FIXTURE TO SEE WIRING
5) USE CONNECTIONS OR CLAMPS AT CABLE ENTRY TO BOXES
6) PLANS AND PERMITS TO BE ON SITE FOR ALL FUTURE INSPECTIONS