Permit: T09CM02243

Parcel: 12512080A


Addresses:

3360 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T09CM02243

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/22/2011 PLUMBING - INTERMEDIATE Approved
10/28/2011 PLUMBING - INTERMEDIATE Partial Approval 1) PLANS SHOW TO INCREASE BRANCH PIPE SIZE TO ACCOMADATE INCREASED DEMAND ON BRANCH. PLAN DOES NOT REFLECT ACTUAL INSTALLATION
2) DISTANCES, SIZES AND DEMAND ? NOT ACCURATELY REFLECTED ON PLAN
3) ENTIRE SYSTEM IS UNDERSIZED
4) CONTACT SW GAS FOR POSSIBLE METER UPGRADE
5) PROVIDE ACCURATE GAS PLA AND ? CORRECT SIZES
6) FLEX MAY NOT BE USED AS CONNECTIVE PIPING
7) PROPER CLEARANCE OF VENTS
8) APPROVED VALVES
9) 2-3 COMP SIONK WASTE AND GREASE TRAP INSTALLED OK
09/12/2011 PLUMBING - INTERMEDIATE Partial Approval
09/08/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CONNECTIONS MADE OK AT FLOOR SINK, HAND SINK AND THREE COMPARTMENT SINK-OK TO COVER U.G.
09/07/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) PROVIDE GAS ISOMETRIC, SHOWING DEVELOPED LENGTH OF EACH SECTION AND TOTAL BTU CONSUMPTION OF EACH APPLIANCE
2) SHOW WHERE GAS PIPING IS TO BE INSTALLED
3) SHOW HOW GAS PIPING IS TO BE INSTALLED
4) SOILS ARE TO WET FOR INSPECTION
09/06/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HS #1 OK TO COVER
2) OK TO COVER UNDER FLOOR WITH EXCEPTION
3) HORIZONTAL VENTING BELOW FLOOD RIM LIMITED TO STRUCTURAL CONDITIONS
09/01/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 4" ABS INSTALLED FOR GREASE TRAP WASTE, FLOOR SINK, AND THE HAND SINK W/4" CO
2) 4" ABS CONNECTED TO EXISTING AS REDLINE ON THE PLAN. OK TO COVER UNDERFLOOR, THIS AREA ONLY.