Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM02243
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/04/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. M/C NOT FROM ANOTHER WIRING METHOD 2. NEW PANELS IN HALL: IDENTIFY NEUTRALS 200.6 3. DERATING 310.15 ( 400 PNL ABOVE) 8 CIRCUITS 4. 400 AMP SWITCH IS BLOCKING WORKING SPACE OF OTHER DISCONNECT + PANEL IS TAPPED INTO BUSS- NO VERIFICATION OF TAP- LABEL DISCONNECT PLEASE HAVE ELECTRICAL CONTRACTOR GO THROUGH PANELS + SWITCH GEAR TO DETECT ANY OTHER DISCREPANCIES AND CORRECT |
|
09/27/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BREAK NEUTRAL AT SERVICE DISCONNECT 250.24 (C) (400 AMP) 2) CONNECT 2ND GROUND ROD |
|
09/15/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE M/C CABLE ABOVE PANEL 2) SEAL COVER FLOOR BOX FROM MOISTURE 3) BOX COVERS GFCI 210.8 B 4) SUPPORT RACEWAYS ABOVE PANELS 5) VERIFY DISCONNECTING MEANS ? 6) MISSING GROUNDING SYSTEM AT SERVICE 7) 400 AMP DISCONNECT ? 8) ROOF GFCI 9) ITEMS NOTED WERE NOT CODE COMPLIANT AT TIME OF INSTALL 10) THIS WAS A WALK THRU PARTIAL INSPECTION |