Permit: T09CM02243

Parcel: 12512080A


Addresses:

3360 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/18/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/04/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. M/C NOT FROM ANOTHER WIRING METHOD
2. NEW PANELS IN HALL: IDENTIFY NEUTRALS 200.6
3. DERATING 310.15 ( 400 PNL ABOVE) 8 CIRCUITS
4. 400 AMP SWITCH IS BLOCKING WORKING SPACE OF OTHER DISCONNECT + PANEL IS TAPPED INTO BUSS- NO VERIFICATION OF TAP- LABEL DISCONNECT

PLEASE HAVE ELECTRICAL CONTRACTOR GO THROUGH PANELS + SWITCH GEAR TO DETECT ANY OTHER DISCREPANCIES AND CORRECT
09/27/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) BREAK NEUTRAL AT SERVICE DISCONNECT 250.24 (C) (400 AMP)
2) CONNECT 2ND GROUND ROD
09/15/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE M/C CABLE ABOVE PANEL
2) SEAL COVER FLOOR BOX FROM MOISTURE
3) BOX COVERS GFCI 210.8 B
4) SUPPORT RACEWAYS ABOVE PANELS
5) VERIFY DISCONNECTING MEANS ?
6) MISSING GROUNDING SYSTEM AT SERVICE
7) 400 AMP DISCONNECT ?
8) ROOF GFCI
9) ITEMS NOTED WERE NOT CODE COMPLIANT AT TIME OF INSTALL
10) THIS WAS A WALK THRU PARTIAL INSPECTION