Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM02230

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/09/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL MAIN BONDING JUMPER IN SERVICE DISCONNECT AND REMOVE EQUIPMENT GROUNDS FROM CT CAN TO SERVICE DISCONNECT. CHECK DIRECTIONS FOR INSTALLING NEUTRAL KIT.
12/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL FUSES PER PLAN
2) INSTALL NEUTRAL BAR IN SERVICE DISCONNECT AS PER INSTRUCTIONS ON DOOR
3) GROUND RODS TO BE MINIMUM 20' APART PER PLANS
4) PROPERLY IDENTIFY NEUTRAL CONDUCTORS TO DISCONNECT
5) BONDING JUMPER TO NIPPLES NOT SIZED PROPERLY NEC 250.102
6) GROUNDING ELECTRODE CONDUCTOR INSTALLED IN METAL REACEWAY TO BE BONDED TO RACEWAY AT BOTH ENDS
7) OK U.G. RACEWAYS FROM SES TO ?
8) MARK SERVICE DISCONNECT
11/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED COMPLETE SET OF APPROVED PLANS, SHEET 1 IS ONLY APPROVED STREET
2) ALL NEW WORK TO BE EXPOSED FOR INSPECTIONS. ALL EQUIPMENT TO BE OPEN FOR INSPECTIONS