Permit: T09CM02186

Parcel: 13101071E


Addresses:

2222 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/05/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
10/04/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) DUCT SMOKE DETECTOR TEST OK
2) EXTEND CONDENSATE TO ROOF DRAINS
3) SECURE ELECTRIC CONDUIT TO A/C #6
4) PROVIDE GFI SERVICE RECEPT ON ROOF
6) 3/8" ID X 24" GAS FLEX NOT ADEQUATE FOR 100,000 BTU
7) FINISH AIR BALANCE
10/01/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DEMO SANITARY VENT IN ROOM TRAINING ROOM PROVIDE HOT WATER INSULATION FOR EMPLOYEE LUNGE
07/19/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK FOR FINAL PHASE I
07/13/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) NEED DUCT SMOKE DETECTOR TEST
2) AIR BALANCE FOR PHASE I OK