Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2010 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* 1) AIR BALANCE REPORT OK 2) DUCT SMOKE DETECTOR TEST OK X 3 3) INTERLOCK BETWEEN MUS & EXH ON KITCHEN HOOKS OK X 2 4) HEST SENSOR INTERLOCK OK X 2 5) SMOKE CONTAINMENT TEST ON HOODS OK X 2 6) COAT ARMOR FLEX ON ROOF WITH PROCECTIVE COATING PER MOVE INSTALLATION INSTRUCTIONS 7) PROVIDE SCREENS IN W/H FLUE AND INTAKE TERMINATIONS 8) DUCT TAPE NOT ALLOWED ON ARMORFLEX EXPOSED TO EXTERIOR 9) AC-3 FLUE EXHAUST TOO CLOSE TO AC-2 INTAKE (O.S.A.) |
|
| 04/05/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 03/24/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 2ND LAYER FIRE WRAP OK |
|
| 03/22/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF FIRE WRAP OK. OK FOR 2ND LAYER OX 2 |
|
| 03/19/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST ON BOTH TYPE 1 DUCTS OK, OK FOR 1ST LAYER OF FIRE WRAP |
|
| 03/18/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) DUCT WRAP ON TWO TYPE 1 DUCTS/DROP OK, COMPLETE WELDING OF TYPE 1 SYSTEM |
|
| 03/16/2010 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST ON TWO (APPROX 36") DROPS, OK FOR BOTH LAYERS OF WRAP ON THESE DROPS ONLY |
|
| 03/15/2010 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* |