Permit: T09CM02126

Parcel: 11901075C


Addresses:

3398 S 6TH AV

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
04/06/2010 MECHANICAL - HOODS Approved IVRS - Inspection :*
1) AIR BALANCE REPORT OK
2) DUCT SMOKE DETECTOR TEST OK X 3
3) INTERLOCK BETWEEN MUS & EXH ON KITCHEN HOOKS OK X 2
4) HEST SENSOR INTERLOCK OK X 2
5) SMOKE CONTAINMENT TEST ON HOODS OK X 2
6) COAT ARMOR FLEX ON ROOF WITH PROCECTIVE COATING PER MOVE INSTALLATION INSTRUCTIONS
7) PROVIDE SCREENS IN W/H FLUE AND INTAKE TERMINATIONS
8) DUCT TAPE NOT ALLOWED ON ARMORFLEX EXPOSED TO EXTERIOR
9) AC-3 FLUE EXHAUST TOO CLOSE TO AC-2 INTAKE (O.S.A.)
04/05/2010 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
03/24/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 2ND LAYER FIRE WRAP OK
03/22/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIRE WRAP OK. OK FOR 2ND LAYER OX 2
03/19/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST ON BOTH TYPE 1 DUCTS OK, OK FOR 1ST LAYER OF FIRE WRAP
03/18/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) DUCT WRAP ON TWO TYPE 1 DUCTS/DROP OK, COMPLETE WELDING OF TYPE 1 SYSTEM
03/16/2010 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST ON TWO (APPROX 36") DROPS, OK FOR BOTH LAYERS OF WRAP ON THESE DROPS ONLY
03/15/2010 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*