Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/07/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE PROPER SUPPORT FOR GAS PIPING 2) PROVIDE APPROVED LOAD CALC FROM CITY OF TUCSON 3) UNIT IS NOT LEVEL. NEED TO CORRECT 4) ALL ROOF TOP DUCT TO BE R-8 (2") INSULATION 5) UNIT NOT PROPERLY WIRED, WIRES NOT CORRECTLY IDENTIFIED 6) CONDENSATE NOT RUN, MUST BE TERMINATED AT AN APPROVED LOCATION 7) ALL DUCT JOINTS MUST BE SEALED 8) ELECTRICAL CONDUIT TO BE BLOCKED UP OFF OF ROOF 9) PROVIDE WATER TIGHT 110 V SERVICE RECT. GFCI ON ROOF WITHIN 25' OF UNIT |
|
| 08/06/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SAFE ACCESS TO ROOF TOP 2) PRESSURE TEST OK |