Permit: T09CM02022

Parcel: 132162960


Addresses:

1504 E EL ATAJO

Inspection Status: Denied

Inspection History: BUILDING - PROGRESS

Date Description Inspector Results Comments
07/31/2009 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR BEDROOM ADDITION IS NOT AS PER DRAWING SUBMITTED-2 X 6'S SPANNING 14'-7" AT 24" ON CENTER-UNABLE TO INSTALL R-30 INSULATION IN THIS SPACE
2) WEEP SCREED AT STUCCO SHALL BE 4" MINIMUM FROM EARTH RAISE WOOD FRAME 6" MINIMUM FROM EARTH. APPEARS WOOD FRAME IS FLUSH WITH GROUND
3) EXPOSE BEAM BETWEEN EXISTING BEDROOM AND ADDITION TO VERIFY SIZE AND CONNECTION AT EACH BEARING POINT
4) CONNECTION AT PORCH 2 X 6 TO FASCIA NOT ALLOWED, SUBMIT AS BUILT TO DSD PLANS EXAMINER FOR APPROVAL
5) HAVE LICENSED ELECTRICIAN VERIFY IN WRITING THAT ELECTRIC IS TO CODE
6) CARPORT ENCLOSURE TO GARAGE SHALL HAVE MAN DOOR BE SELF CLOSING