Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T09CM01970

Parcel: 13101054A


Addresses:

4702 E 22ND ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/14/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/10/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
05/27/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE AIR BALANCE REPORT
2) A/C UNIT OVERFUSED
3) PROVIDE HAIL GUARD AS PER PLANS
4) OK TO TERMINATE CONDENSATE TO THE MOP SINK
5) PROVIDE COPPER AS PER PLANS
6) BUILD TRAP PER PLANS