Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ELECTRIC |
|
| 06/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONNECT EQUIPMENT GROUND TO POLE LIGHT 2ND FROM EAST 2) CANNOT SUE TECH SCREWS FOR CONNECTIONS OF EQUIPMENT GROUNDS IN DISCONNECTS 3) USE PROPER COLOR CODING AT WIRES INSTALLED IN RACEWAYS. 120/208V COLORS AT 277/480V COLORS 4) MISSING EM LIGHT 5) MISSING PLATE ON RECEPT IN MECH ROOM 6) BLANK OPEN BOXES. INSTALL COVERS ON LIGHT POLES 7) WHITE AND GREEN TO BE USED ONLY FOR NEUTRAL OR EQUIPMENT GROUND UNLESS CONTROL WIRING |
|
| 05/27/2010 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL ELECTRIC 2) NEED 6" CLEARANCE ON XFMR 3) WIRE EM LIGHTS PER PLAN, MISSING OUTDOOR EM'S 4) NEED SIESMIC WIRES ON LIGHT FIXTURES AND ATTACH TO GRID 5) DISCONNECTS TO BE NO MORE THAN 6'-7" TO CENTER OF HANDLE IN UP/ON POSITION UNLESS ON SAME LEVEL AS MOTOR 6) HAVE APPROVED PLANS ON SITE AND IN ORDER |