Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2010 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/25/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MEETING TO DISCUSS PROJECT |
|
| 05/11/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND STEEL AND WATER TO SERVICE 3/0 2) WIRE XFMR AS DISCUSSED 3) NEED TO POST BOND TO GET POWER RELEASED TO POWER COMPANY |
|
| 04/28/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CEILINGS AND WALLS IN BLDG ALL OK |
|
| 04/26/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) MEETING TO DISCUSS CORRECTIONS |
|
| 04/21/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL JUNCTION BOXES TO BE ACCESSIBLE 2) CLOSE ALL OPEN KNOCKOUTS IN BOXES 3) STRAP EMT WITHIN 3' OF CONNECTIONS 4) STRAP MC CABLE WITHIN 12" OF CONNECTIONS |