Permit: T09CM01842

Parcel: 12215161A


Addresses:

3146 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Permit Number - T09CM01842

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2009 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
1) OK TO CLEAR
2) RECEIVED LETTER FROM ELECTRIC CONTRACTOR AS REQUESTED
10/13/2009 ELECTRIC - RECONNECT Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER FROM ELECTRICAL CONTRACTOR TO VERIFY A/C SYSTEM HAS BEEN CHECKED OUT AND IS SAFE TO RE-ENERGIZE SES, LOCK OUT & TAG OUT ALL CIRCUITS AND FEEDERS EXCEPT GFI PROTECTED RECEPTS. DO NOT ENERGIZE PANELS OF FEEDERS PRIOR TO INSPECTORS APPROVAL
2) SEE NOTES FROM PREVIOUS INSPECTION
10/06/2009 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTES ON PLAN-CONTR. TO VERIFY GROUNDING SYSTEM IS INTACT (E-2)
2) SES EQUIP APPEARS TO BE IN NEED OF CLEANING AND OVERALL MAINTANENCE (PM) CONTR. TO VERIFY CONDITION AND ADJUST/REPAIR AS NECESSARY PRIOR TO APPROVAL TO ENERGIZE. GFI PROTECTION REQUIRED FOR PERSONAL