Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09CM01656

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/06/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/16/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 1" THICK ARMAFLEX ON REF. PIPING PER PLANS
2) VERIFY C.U. PLATFORM HAS 6" SOUND INSULATION
3) VERIFY DUCT FIRE/SMOKE DAMPER ACTIVATION
4) PROVIDE APPROVED TERMINATION OF CONDENSATE TUBE TO COPPER PIPING (BARBED FITTING WITH CLAMP)
5) PROVIDE 2" DUCT FILTERS PER PLANS
6) PROVIDE ACCESS DOORS AT DAMPERS
7) PROVIDE Z FILTERS PER PLANS
8) FIRE/SMOKE INTERLOCK WITH FAN
9) ARMAFLEX EXPOSED TO EXTERIOR TO BE COATED PER PLANS
10) ELECTRICAL CONNECTORS LOOSE (SEAL TITE)