Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01653
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK ALL ELECTRIC |
|
12/13/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
12/02/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
09/14/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 503-512 TO USE |
|
09/10/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY GROUNDING FOR FLOOR BOXES 2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 3) PROPERLY LABEL PANEL COVERS 4) OK POWER POLES ROOM 500 |
|
06/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 300 SOUTH FOR USE 2) OK WALLS ROOM 601 |
|
05/03/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
04/30/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT FLEX PER CODE |
|
04/29/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 223 & 224 EXCEPT ENVIRO AIR NOTE |
|
04/01/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
01/11/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FIXTURE WHIPS NOT TO BE LAYING ON PIPES 2) SUPPORT WIRE FOR EXIT SIGN 3) FINISH VDV AND PANEL DIRECTORIES ALL AREAS 4) OK ROOMS #204,218 AND 216 EXCEPT POWER POLES AS NOTED 5) OK 300 AND 208 EXCEPT AS NOTED |
|
01/04/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK 203, EXCEPT VDV 119 AND PERMANENT PANEL 120, 120A DIRECTORIES AND 205-207 208: 1) CORDS NOT ALLLOWED ABOVE CEILING-INSTALL PER MFG INSTRUCTIONS 2) BOXES MORE THAN 1/4" 314.20 3) EXIT SIGN NOT WORKING ROOM 300 4) FINISH CORRIDOR 201 |
|
11/25/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED PERMANENT PANEL DIRECTORIES 2) NEED HANDLE TIES OFFICE FURNITURE 605.7 3) SUPPORT ALL POWER POLES 4) OK POWER FOR AH-1 5) LABEL EQUIPMENT AND DISCONNECTS 6) OK PARTITION WALL ROOMS 203 AND 208 |
|
11/16/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
11/04/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) MISSING 2 X 4 LIGHTS ROOM J0244 2) OFFICE FURNITURE TO BE AS PER CODE 605.7 3) PANEL SCHEDULES TO BE AS PER 408.4 4) FINISH SECURE DATA AT CABLE TRAYS 5) OK ELECTRIC FOR PARTIAL 6) WEST OF COLUMN 'J'-RECALL AS COMPLETING NOTED ITEMS 7) OK TO MAIN LUGS PANELS 8) L/H 5-2A AND L/H 5-2 9) NOTE: TIGHTEN MFG LUGS AND NEED ILLUMINATION |
|
11/03/2009 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
10/30/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |