Permit: T09CM01653

Parcel: 140430130

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM01653

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/16/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK ALL ELECTRIC
12/13/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/02/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
09/14/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK ROOMS 503-512 TO USE
09/10/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) VERIFY GROUNDING FOR FLOOR BOXES
2) BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
3) PROPERLY LABEL PANEL COVERS
4) OK POWER POLES ROOM 500
06/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK 300 SOUTH FOR USE
2) OK WALLS ROOM 601
05/03/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT FLEX PER CODE
04/29/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK 223 & 224 EXCEPT ENVIRO AIR NOTE
04/01/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
01/11/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FIXTURE WHIPS NOT TO BE LAYING ON PIPES
2) SUPPORT WIRE FOR EXIT SIGN
3) FINISH VDV AND PANEL DIRECTORIES ALL AREAS
4) OK ROOMS #204,218 AND 216 EXCEPT POWER POLES AS NOTED
5) OK 300 AND 208 EXCEPT AS NOTED
01/04/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK 203, EXCEPT VDV 119 AND PERMANENT PANEL 120, 120A DIRECTORIES AND 205-207
208:
1) CORDS NOT ALLLOWED ABOVE CEILING-INSTALL PER MFG INSTRUCTIONS
2) BOXES MORE THAN 1/4" 314.20
3) EXIT SIGN NOT WORKING ROOM 300
4) FINISH CORRIDOR 201
11/25/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED PERMANENT PANEL DIRECTORIES
2) NEED HANDLE TIES OFFICE FURNITURE 605.7
3) SUPPORT ALL POWER POLES
4) OK POWER FOR AH-1
5) LABEL EQUIPMENT AND DISCONNECTS
6) OK PARTITION WALL ROOMS 203 AND 208
11/16/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
11/04/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) MISSING 2 X 4 LIGHTS ROOM J0244
2) OFFICE FURNITURE TO BE AS PER CODE 605.7
3) PANEL SCHEDULES TO BE AS PER 408.4
4) FINISH SECURE DATA AT CABLE TRAYS
5) OK ELECTRIC FOR PARTIAL
6) WEST OF COLUMN 'J'-RECALL AS COMPLETING NOTED ITEMS
7) OK TO MAIN LUGS PANELS
8) L/H 5-2A AND L/H 5-2
9) NOTE: TIGHTEN MFG LUGS AND NEED ILLUMINATION
11/03/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/30/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*