Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM01653
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/16/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/16/2010 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/13/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEED ARC SHIELDS AT RECEPT COUNTER 2) FINISH 409 3) OK ROOMS 403-408, 410-419, 424-428, 502 AND 407 ABOVE CEILING AND FOR USE |
|
12/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK POWER POLES 300 2) OK ABOVE CEILING 424-428,502 ELECTRIC 3) OK PANEL "LA.5" LB-5 |
|
11/29/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ELECTRIC ROOM 600 |
|
11/19/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING ROOMS #406,410,412,414,415,418-421 AND 303 2) OK MAKE UP PANELS L/E-4,L/E-4A,LD-5,L/C-5 AND H/E-4.5 |
|
11/17/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT BOXES AND CONDUITS PER CODES 2) NEED SUPPORT WIRES ON ALL FIXTURES 3) MANUFACTURERS CLIPS TO BE EFFECTIVE 4) SEAL UNUSED RACEWAYS ABOVE PANEL |
|
09/14/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/10/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
08/09/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
08/05/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/30/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH POWER POLES 2) OK ABOVE CEILING EXCEPT AS NOTED |
|
06/03/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK POWER POLE 300 SOUTH OK PANEL H/B-2 MAKE UP |
|
05/21/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/03/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK 212 TO USE 2) OK E2,F2,22 & F3 CONDUITS IN COLUMNS |
|
04/30/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/29/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/01/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH OUTSIDE OF PANEL LABELING AND PANEL DIRECTORIES 2) OK ROOMS 217, 201, 221, 222 & 301 OCCUPANCY ROOM 212: 1) FINISH VDV AND POWER POLES ABOVE CEILING |
|
03/31/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
03/26/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/25/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 201, 222, 224 AND 221 2) FINISH VDV CABLES AND ANSWER QUESTION FOR #1 ON 3/17/10 |
|
03/23/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK POWER POLES #6 & 5 2) OK #3 TO #4 ROOM 301 3) FINISH VDV AND POWER POLES |
|
03/22/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
03/17/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
03/04/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING ROOM 219, EXCEPT VDV CABLING |
|
03/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK EAST WALL ROOM 222 2) OK ABOVE CEILING 144 |
|
03/01/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
02/16/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUPPORT VDV CABLING PER 725.3 & 24 ROOM 217 2) OK WALLS 219 & 114 3) OK ABOVE CEILINGS: #215 & 217 EXCEPT AS NOTED, 111B 4) OK CONDUIT ABOVE GRID 114 |
|
01/11/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/04/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/29/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/17/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ? EXISTING TO BE SUPPORTED 770.24 AND 770.3 2) SUPPORT FLEX CONDUIT PER CODE 3) OK WALLS 202 4) OK ABOVE CEILING AFTER CORRECTION 205-207 |
|
12/16/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/14/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/10/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/08/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABLING 725.3 & 24 AND 800.3 & 24 2) OK ROOMS #116-119 AND 120-121, EXCEPT AS NOTED |
|
12/07/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/04/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/01/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/25/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/16/2009 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
11/13/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SECURELY FASTEN TO GRID 410.16 2) FINISH VDV CABLING 3) FINISH POWER POLES 4) OK TILES OTHER AREAS, NOTE: SUBJECT TO OTHER TRADES |
|
10/30/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILINGS ROOMS #110,109,108,107,106,105 AND 103 |
|
10/26/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TO ENERGIZE T-12, L/K-4-UPS, L/J, 5-25A NEED REVISED PLAN FOR T-12 2) OK. GILINGS RMS 100 & 101A 3) GROUND FAR FEEDER TAPS TO BE PER 250.122 (G) |
|
10/05/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
09/18/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |