Permit: T09CM01648

Parcel: 11706183B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T09CM01648

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS MADE OK
2) PLUMBING FINAL OK
10/16/2009 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) STERILIZATION REQUIRED PER UPC 609
2) LOWER ICE BACKFLOW PREVENTOR TO 5'
3) SECURE SUPPLY TUBING, PROVIDE RIDGID DRAIN PIPING WITH SLOPE AND AG
4) DOME STRAINERS AT FS
5) SUPPORT CW SUPPLY AT WATER HEATER, INSULATE HOT WATER PIPING 1" MIN AT AIR CAPS
6) REDUCTION OF DRAIN SIZE AND DRAINAGE FITTINGS AT 3 ? SANITIZE COMPARTMENT