Permit: T09CM01636

Parcel: 10706027E


Addresses:

1306 W MIRACLE MILE

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
06/28/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/17/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 2ND FLOOR ABOVE CEILING OK TO COVER DUCT
04/26/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
04/05/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :* LAB MIDDLE 1T FLOOR DUCT OK TO COVER 2ND FLAR SOUTH WALL LINED OK TO COVER
03/29/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) LAB WEST 1ST FLOOR NORTH SIDE DUCT ABOVE CEILING OK TO COVER
2) LAB EAST 1ST FLOOR NORTH SIDE DUCT ABOVE CEILING OK TO COVER
3) INSULATE ALL UN-LINED SQUARE TO ROUNDS ON SUPPLY
03/11/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
03/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) LINEAR CANS ARE TO BE INSULATED
2) VAV-124 HAS NO ACCESS TO CONTROL PANEL
3) NO COMBUSTIBLE MATERIALS IN RETRUN PLENUM ( ? BLOCKS)
03/03/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WOMENS AND MENS RESTROOMS 1ST FLOOR OK
03/02/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WOMEN'S AND MEN'S RESTROOMS 2ND FLOOR SUPPLY AND EXHAUST OK
2) 100 PSI HYDROSTATIC ON HOT WATER REHEAT FROM SHUT OFF VALVES TO VAV'S AND LS UNITS OK INSULATE 1ST FLOOR ONLY
02/10/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/09/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :
1. ALL FIRE/SMOKE DAMPERS ARE TO BE FRAMED OUT ON ALL SIDES PER MASNUFACTURES INSTALLATION INSTRUCTIONS, PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR NEXT INSPECTION ALL DAMPER FRAMING TO BE EXPOSED FOR INSPECTION
02/08/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
HARD LIDS 1ST GEAR OK
DUCT 1ST FLOOR OK TO INSULATE
02/02/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
01/06/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/16/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) FUTURE HYDRO PIPING FROM MECH ROOM TO FIRING RANGE PRESS. TEST OK, OK TO INSULATE
11/23/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUSPENDED ROUGH DUCT MAIN TRUNK LINE 2ND FLOOR MEDIUM PRESSURE OK TO INSULATE
11/15/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) MED PRESS 1ST FLOOR OK TO WRAP