Inspection Status: Approved
Inspection History: MECHANICAL - HYDRONIC PIPING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2011 | MECHANICAL - HYDRONIC PIPING | Approved | IVRS - Inspection :* | |
| 05/17/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 04/27/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* HYDRO TEST TO AHU'S IN PENTHOUSE OK. OK TO INULATE PIPING IN PERNHOUSE |
|
| 04/26/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 03/28/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO TEST ON REMAINING PIPING OK |
|
| 03/22/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 2ND FLOOR SOUTH WALL LINEARS OK TO COVER 2) 2ND FLOOR NORTH EAST HYDRO OK, OK TO INSULATE |
|
| 03/11/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) LINEAR SLOT DIFFUSERS SOUTH WALL 1ST FLOOR, OK TO COVER 2) 2ND FLOOR NORTH END OF BLDG HYDRO TEST THRU THE COILS TESTED OK AT 100 PSI + |
|
| 01/14/2011 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HYDRO TEST ON 1ST FLOOR VAV AND LS UNITS OK TO INSULATE 2) PVC COLD WATER FOR COOLING EQUIPMENT OK TO INSULATE |
|
| 12/28/2010 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) HEATING HOT WATER PIPING 2ND FLOOR LAB EAST MAINS AND BRANCHES-OK TO INSULATE |
|
| 12/22/2010 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* | |
| 11/12/2010 | MECHANICAL - HYDRONIC PIPING | Partial Approval | IVRS - Inspection :* 1) 1ST FLOOR EXITING MECHANICAL ROOM OUT TO BRANCH'S HYDRO TEST OK, OK TO INSULATE THIS AREA ONLY |