Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2011 | ELECTRIC - FINAL | Approved | ||
| 08/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 07/26/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY LISTING AIR SCIENCE EQUIPMENT ROOM 245 2) FILL UNUSED CONDUIT OPENINGS AND BOX COVER 3) OK TO TILE, EXCEPT AS NOTED 4) OK ROOM 246, EXCEPT AS NOTED |
|
| 07/19/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WRITING ON LISTING AND LABELING VERIFICATION OF EQUIPMENT AS STAMPED ON APPROVED PLANS, ALSO SPEC 260500-3 1.5 C. ALL OTHER ITEMS CORRECTED |
|
| 07/11/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED COVERS CANOPY WEST AND EAST 2) BOND POLES TO GROUNDING EQUIPMENT CONDUCTOR 250.54 3) BOND JUNCTION BOXES FOR FRONT SITE WALL LIGHTS 4) FINISH SPACING VDV AT WALK IN BOX 5) OK BOLLARDS 6) OK SERVICE OF 120V EQUIPMENT WALK-IN BOX |
|
| 07/07/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH PREVIOUS ITEMS |
|
| 07/06/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY LISTING AND LABELING FOR PASS THRU REFRIDGERATION UNIT-166 AND BULLET RECOVERY SYSTEM-176 2) OK RO9OM 146-168, 170-183-EXCEPT AS NOTED |
|
| 06/30/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/29/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE VERIFY LISTING AIR SCIENCE-226, ALSO FINGER PRINT CABINETS 2) OK ROOMS 230,231,225-228,201,202,204-212 3) OK PVC CONDUIT AT PALM TREES |
|
| 06/28/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) VERIFY LISTING STATIC PASS THRU'S-FIXTURE LISTED AS PORTABLE, ALSO NO GROUNDING UNDER CABINET LIGHTS 2) FILL UNUSED OPENINGS IN PLUG HOLDS (215) 3) |
|
| 06/27/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) LABELING OF CIRCUITS AND EQUIPMENT 408.4 2) BOXES IN COMBUSTIBLES 314.20 3) NEED DISCONNECTING MEAN AT CONDENSING UNIT-WALK IN 4) PLEASE VERIFY WALK IN SEALS 300.7 5) GROUND WALK IN FLOURESCENT LIGHTS 6) OK ROOM 232-234,236,239-244,247-250 7) OK MECHANICAL AREA (ROOF) AND ROOM 169 8) OK ROOF EQUIPMENT EXCEPT UPPER LEF UNITS FOR CLEARANCES |
|
| 06/23/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CDWP'S CORRECT SIZE WIRE CONNECTORS 2) CLIMATEC FITTINGS & CONDUTS SUPPORTS |
|
| 06/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PENTHOUSE: 1) MISSING COVER AND FILL UNUSED OPENINGS 2) HRP-2 WILL NOT RESET 3) LOOSE FITTINGS AT ? 4) SUPPORT CONDUITS 5) LABEL MAIN ROOF: 1) FILL UNUSED OPENING 2) FINISH LIGHTING PROTECTION 3) PROVIDE SAFE ACCESS TO LEF-1 4) BOND OVER 250V LEF-4 |