Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM01612
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/25/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RETURN INSP. 3:30 PM AFTER HRS. INSP. PER OWNER REQUEST PAID $150.00 MONEY ORDER #68419751950 |
|
06/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* METERS TO COMPLY WITH 430.32 NEC - BAKERY EXH. FAN 4HP NON-THERM. PROTECTED - DELI EXH. FAN OK 602-723-2338 (GRANT) |
|
06/23/2009 | ELECTRIC - FINAL | Correction Required | EM. CALL OUT (3:08 PM) DNR ON SITE/TFD ON SITE 1. OWNER TO OBTAIN 1-HR REPAIR PERMIT ELEC & MECH. 2. APPEARS EXH. FANS ON ROOF FOR KITCHEN EQUIP. BLOWING FUSES, OWNER LOCKED/TAGGED OUT CIRCUIT BREAKERS (KITCHEN FANS) 3. CALL FOR INSPECTIONS WHEN READY USE A QUALIFIED OR LICENSED ELECTRICIAN & MECH. CONTR. |