Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/31/2009 | FIRE - FINAL | Approved | Approved 7/31/09. | |
| 07/24/2009 | FIRE - FINAL | Denied | 1. Need Fire Alarm annual inspection report. 2. Remove multi locks on panic hardware in lunch room. 3. Two portable fire extinguishers needs to be serviced/repaired. 4. Ceiling tile in drama room needs to be replaced. 5. Door in drama room needs to be unblocked. 6. Copier room extension cord is being used as permanent wiring. 7. Remove top shelf from archived storage room to allow for 18 inches from sprinkler head. 8. Relocatable power tap needed in staff kitchen. 9. Upstairs 'Art Room' portable fire extinguisher needs to be mounted, serviced/repaired. 10. Service/repair emergency exit lights in upstairs hallway. 11. Ken Po fight room needs electrical cover plate on East wall. 12. S/E exit door in drama room needs to remove sign which says 'Do Not Use This Door'. 13. Exit door on East wall of North hallway remove u-bolts. 14. North/West hallway remove u-bolt from exit door. 15. Storage area in science room remove box with cups which is blocking sprinkler head. |