Permit: T09CM00849

Parcel: 117050020


Addresses:

400 N 2ND AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T09CM00849

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
12/30/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ITEMS 1 & 2 DATED 12/16/10 HAVE BEEN CORRECTED
12/29/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
12/16/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE HYDRO TEST ON TOTAL SYSTEM AS NOTED 10/28/09
2) PROVIDE DUCT SMOKE DETECTOR TEST ON ALL AIR HANDLERS MOVING OVER 2000 LFM (5)
3) PROVIDE TESTING OF FIRE/SMOKE DAMPERS
4) VERIFY 2" INSULATION IN RETURN PLENIUMS AT GYM AREA
5) PROVIDE AIR BALANCE REPORT
12/14/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/18/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DUCT ABOVE CEILING ON NORTH END OF GYM OK TO COVER
07/28/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GIRLS LOCKER ROOM AREA HARD LIDS OK TO COVER DUCT THIS AREA
06/15/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/20/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HW S/R TESTED OK TO SAME LOCATIONS AS CHW S/R DATED 4/7/10 NOTE CORRECTION C.L. "H" AS NOTED ON 4/7/10 IS ACTUALLY C.L. "K"
04/07/2010 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNDERGROUND HYDRO TESTING ON CH S/R FROM BLDG A TO STUB UP AT C.L. "H" THRU TO A.H-B5, AH.B-1 AND B-2 STUB UP AND ON TO CENTRAL PLAN OK AT 100 PSI+
10/28/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RECEIVED LETTER FROM ENGINEER ALLOWING AN AIR TEST
2) A 100 PSI HYDROSTATIC TEST WILL STILL BE REQUIRED AFTER ALL PIPING IS INSTALLED
10/15/2009 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) AIR TEST ON HYDRONIC PIPING NOT ACCEPTABLE
2) CANNOT CONFIRM PIPE IS HOLDING PRESSURE
3) BACKFILL AT OWN RISK
10/13/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROVIDE A MIN, 100 PSI HYDROSTATIC TEST ON ALL HYDRONIC PIPING
10/05/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO BACK FILL UNDERGROUND HYDROLIC PIPING UP TO POINT DESIGNATED ON PLANS 10/02/09
10/02/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO INSULATE FITITNGS (PRESSURE TEST OK) UP TO SOUTH END OF BLDG HYDRO FROM EXISTING GYM