Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM00849
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/2010 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/14/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS 2) HAVE PLUMBER COMPLETE HIS PUNCH LIST PRIOR TO CALLING FINAL-TAKE CARE OF CONDITIONS ON PERMIT 3) OPEN UP EWC FOR INSPECTION 4) PROVIDE METHOD OF STERILIZATION 5) PROVIDE CLEAN BACTERIA REPORT 6) PROVIDE PETITION OF APPEAL FOR WATERLESS URINALS NOTE: REQUIRE 15" FROM SIDEWALL TO CENTER OR OBSTRUCTION |
|
09/09/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NORTH AND SOUTH MECHANICAL ROOM OK TO CONCRETE S.T.O.I. |
|
08/26/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NORTH AND SOUTH MECHANICAL YARD PLUMBING FLOOR SINKS OK TO COVER & SEWER CONNECTION OK |
|
08/18/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) REQUIRE BRASS ADPT BETWEEN CAST IRON AND COPPER 2) MAKE ALL CONNECTIONS AND TEST ALL PIPE & FITTINGS 3) HORIZONTAL CLEANOUT EXTENSION TO BE THRU A WYE BRANCH FITTING |
|
07/30/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER DRINKING FOUNTAIN AT B-104 |
|
07/28/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) A + B-104 DRAINAGE PIPING TO BE INSTALLED AT 2 PERCENT SLOPE |
|
07/26/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) DRINKING FOUNTAIN B-104 2) PIPE COVERED UNABLE TO CHECK GRADE OR CONNECTIONS |
|
07/15/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/13/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) N/H ROOF DRAIN AND OVERFLOW DRAIN TO JUST OUTSIDE BLDG OK 2) WHO SAW RAIN HEADER PIPING FROM BLDG TO STORMWATER CONNECTION U.G. |
|
07/12/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) LOCKER ROOM RESTROOMS, FACULTY BATHROOMS AND RESTROOMS #140 & 141 2) PLUMBING IN WALLS OK-NEED TO RECHECK INSULATION ? ? |
|
07/07/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CHECK YOUR PERMIT CARDS TO CALL IN THE CORRECT INSPECTION 2) PERMIT CARD #T09CM00849 DOES NOT INCLUDE 03050 GAS PRESSURE TEST, NOR DOES THE PLAN SHOW ANY GAS PIPING |
|
04/19/2010 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 2 VENTS IN MECHANICAL EQUIPMENT ROOM EXTENDED 10' UP WALL OK TO COVER 2) 3/4" WATER STUBBED TO BELOW GRADE OK |
|
04/05/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CHILLED WATER IS MECHANICAL |
|
03/31/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) UNABLE TO LOCATE WORK AREA 2) NOBODY IN BLDG 3) NOBODY IN THE OFFICE |
|
02/16/2010 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
10/15/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) HOT WATER AND HOT RETURN, FROM THIRD TURN, EXTENDED INTO AND STUBBED UP INTO BLDG OK 2) 100 POUND TEST OK 3) OK TO COVER UNDERGROUND |
|
10/06/2009 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TYPE K COPPER STUBBED IN AT B102 AND B107 |
|
10/02/2009 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |