Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2010 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* 1) CONTRACTOR TO LOCK OUT-TAG OUT EQUIP. AS NECESSARY-ANY AUTHORIZE PERSONS TO HAVE ACCESS TO ELECTRICAL 2) RECEIVED GFI MAIN SES BREAKER TEST REPORT |
|
| 04/23/2010 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE GFI MAIN BREAKER AND FIELD TEST PER 230.95 A THRU C NEC 2) PROVIDE GENERATOR TEST PRIOR TO OPERATION AT FINAL |