Permit: T09CM00849

Parcel: 117050020


Addresses:

400 N 2ND AV


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T09CM00849

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2010 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
10/05/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) MECHANICAL ROOMS (2)-TOPPED OUT-OK TO GROUT AND CAP
09/28/2010 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
09/24/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 2ND LIFT ON MECH YARDS
09/21/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST LIFT ON SOUTH MECH YARD
09/20/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH MECH YARD 1ST LIFT OK
03/03/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALL AT 16' (TOPPED OUT) GL: 1/F-G, G/2-3, WALL AT 31'-4" (TOPPED OUT) GL; 10/E-F OK TO GROUT PROGRESS AREAS
03/01/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL 28' 10/E-F, GL 12' 1/F-6
02/24/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
24' GL 10/E-F, GL 1/F-G 8'
02/22/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 16' LIFT GL E-F/10 TOP OUT GL 10/D-E
02/22/2010 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
NOT READY INCOMPLETE
02/17/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 8' LIFT GL E-F/10
02/16/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) INTERIOR WALLS (WEST PORTION) AT 14'-8" OK TO GROUT PROGRESS AREAS
2) ENSURE PLACEMENT OF DOWELS AT G/1-DETAIL #107
02/10/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) TOP OUT GL C-D/10
02/09/2010 REINFORCED MASONRY PRE-GROUT Partial Approval GL 10/C-E 28' GL 11/D-E 29'-4"
02/08/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 16' TOP OUT; G.L. 11/F-K; F/10-11; K/7-11; OK TO GROUT PROGRESS AREAS
02/04/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STEM WALL AT 28"-40" DTAIL #139, PAGE S4.02 G-L: .5/G-H, H/.5-3; G/.5-1 OK TO GROUT PROGRESS AREA
02/02/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) CMU WALLS AT 12'-8"; 6.1/G-L; 7/G.5-L; G/5.5-11; G.5/5.1-9; 7.1/G-H; 9.5/G-H CMU AT 24'; 12/E-F; F/11-12 OK TO GROUT PROGRESS AREAS
02/01/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CMU WALLS SW PORTION @12'8" - GL
5/F-K; F/1-5; K/3-5; 3/H.5-K; H.5/1-3
OK TO GROUT PROGRESS AREAS
01/28/2010 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) MISSING VERTICAL REBAR
01/25/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12' GL 7/G-K, 7-11/G, 20' LIFT GL D-E/11
01/19/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL 2-7/G-K 12'-8" LIFT, GL D-E/10 16' LIFT
01/13/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 2ND LIFT GL 7/G-K
01/12/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12' LIFT GL D-E/11-10, GL 11/F-K, 7/F-L, G-H/7-11 2ND LIFT
01/07/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST LIFT GL 2-11/K, 6.3/G-L, 5-?, 6.5/2-4, 2.5/G-K, G/2-7
01/06/2010 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST LIFT GL 11/F-K, 7/F-K, K/7-11 AND G-6.5/8-11
12/31/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 8' LIFT GL D-C/11, ROOMS B108,B107 & B1037
12/21/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) TOP OUT B-100
12/14/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
TOPOUT GL 7.1/A-B, A/4-7.1, 5.5/A-C, 12'8" GL 1-4/B-C
12/10/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL F/1Q-1; 1/C-F TOP OUT
12/09/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12'-8" AT ROOM 104 & 102B, B101 & B100, TOP OUT GL C/1-10
12/08/2009 REINFORCED MASONRY PRE-GROUT Cancelled CANCELLED PER GENERAL CONTRACTOR JOHN #904-1042
12/08/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
12/04/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) SOUTH WALL AT 29'-8"; GL F/1-10-OK TO GROUT PROGRESS AREA
12/03/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) WILL RECALL FOR 12/4
12/02/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
11/24/2009 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DO NOT HAVE PROPER LAP ON REBAR
11/24/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 24' LIFT GL F/1-10, 1/C-F, C/1-10
11/19/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 20' 8" GL C-D/10 AND F/1-10
11/18/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 20'-8" LIFT GL 1/C-F
11/17/2009 REINFORCED MASONRY PRE-GROUT Partial Approval 1) 20'-8" GL C/1-10, 16'-8" GL 10/C-E
11/16/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 16'-8" GL F/1-10
11/13/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 16' 8" LIFT GL 1-10/C., 1/C-F
11/10/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 12' 8" GL 1/D-F, F/1-10
11/05/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL 1-10/C, 1/C-D AND 10/C-E
11/02/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 2ND LIFT GL 1/C-F, C/1-10, 10/C-F PLEASE WATCH ALL OVERLAPS FOR NEXT LIFT
2) 2ND LIFT GL F/1-10
10/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
PARTIAL 1ST LIFT
GL F/1-10, 4.1-7/A, A-C/4.1, 7/A-B, B/7-9
10/21/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL 1/C-F, C/1-10, 10/X-E, 11/D-E, D/10-11 AND E/10-11
10/01/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
CMU STEM WALL
GL 1.0/F.0-E.0, C.0/1.0-7.0, 2.0/C.0-B.0, B.0/2.0-4.0
09/30/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) OVER LAPS TO SHORT
09/28/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) GL 3.1-5.1/K, 5.2-6.3/L, 6.3-12/K, K-L/6.3 AND 5.2/K-L
09/25/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) MISSING REBAR