Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/02/2011 | BUILDING - PROGRESS | Approved | IVRS - Inspection :* | |
| 04/09/2010 | BUILDING - PROGRESS | Cancelled | CANCELLED PER HOMEOWNER SUSAN #822-4297 | |
| 04/09/2010 | BUILDING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER OFFICE |
|
| 10/14/2009 | BUILDING - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE ALL SIDING EXT. WALLS PROPERLY/SIDING MAY NOT REST ON GROUND 2) EXPOSE ALL BOTTOM PLATES 3) CARPORT/STORAGE LAUNDRY 4) 2 X 4 RAFTERS OVER SPANNED 5) PROVIDE PROPER HANGERS THRU-OUT. PROVIDE BEAM TO POST HARDWARE 6) LEDGER TO MASONRY BOLTS OVERSPANNED 7) EXPOSE POST FOOTERS TO VERIFY DEPTH 8) FRAMING TO STORAGE LAUNDRY SUB-STANDARD 9) HAVE LICENSED ELECTRICIAN SUBMIT LETTER HEAD. ALL ELECTRICAL WORK TO CODE TO INCLUDE 220 TO DRYER AND ALL ROMEX ADDED TO ROOMS DEN/BEDROOM: 1) HAZARDOUS ELECTRICAL WIRING EXPOSED THRU-OUT NOTE 7 FROM CARPORT 2) WATER HEATER LACKS REQUIRED COMBUSTION RELIEF TO EXTERIOR. EXTEND TPR LINE TO EXTERIOR OR PAN WITH APPEAL 3) ROOM MISSING OUTLETS PER CODE 4) MISSING SWITCHED FIXTURE TO EXIT DOOR 5) GFCI PROTECT BATH OUTLETS 6) SMOKE ALARMS ALL BEDROOMS AND HALLWAYS 7) REAR BATH DOES NOT APPEAR TO BE EXISTING |