Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/14/2009 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/28/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/27/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/24/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* | |
| 08/12/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) PROVIDE ACCESS DOOR FOR COND. CLEANOUT ON RIGHT SIDE OF DISHWASHER HOOD-OK TO ROCK LID IN DISHWASHER AREA 2) OK TO ROCK STORAGE BEHIND HOOD-OK TO ROCK KITCHEN |
|
| 08/11/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 2ND LAYER FIRE WRAP OK 2) PROVIDE PROPER SLOPE ON DISHWASHER EXHAUST |
|
| 08/10/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) 1ST LAYER OF LOWER SECTION OK, OK FOR 2ND LAYER OF FIRE WRAP |
|
| 08/07/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST ON GREASE DUCT COMPLETE-OK TO FIRE WRAP |
|
| 08/06/2009 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1) SMOKE TEST ON 48" DROP OK, OK TO DBL WRAP THIS SECTION 2) OK FOR 1ST SECTION OF DUCT DROP TO BE INSTALLED |
|
| 08/05/2009 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 1) SMOKE TEST FAILED |