Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/22/2010 | ELECTRIC - FINAL | Approved | ETL LISTING FOR AIR MACHINE ACCEPTED. WINDOW SHUTTERS ACCEPTED AS CODE COMPLIANT WITHOUT FURTHER LISTINGS. |
|
| 05/07/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NO WORK PROGRESS 2) WORK HAS BEEN INSTALLED PER NEC 3) UNLISTED EQUIPMENT APPROVAL SUBJECT TO OTHER |
|
| 03/19/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #2 & 3 |
|
| 03/16/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FORGEIGN SIGN: 1) SUPPORT LV WIRE OFF OF GRID AND NEED GROUND EQUIPMENT CONDUCTOR 600.7 2) ROLL UP MOTOR HAS A RECOGNIZED COMPONENT LABEL ON UNIT NOT A LISTING MARK 3) VERIFY LISTING OF AIR PUMP 4) OK ROOF AND PREVIOUS NEEDED ITEMS |
|
| 03/10/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) PLEASE VERIFY LISTING AND LABELING FOR CREAMER 2) ALL INTERVENING RACEWAYS AND FITTINGS 501.30 3) SODA FOUNTAIN SIGN TOB E PER 600.3, 4, 5 & 6 4) GROUND OUTDOOR JUNCTION BOX 5) FINISH #2 & 4 PREVIOUS ITEMS 6) NEED LADDER TO ACCESS TOP OF WALK IN ROOF: 1) NEED DISCONNECTING MEANS SMALL CONDENSOR 2) PROTECT SEAL TITE FROM SHARP METAL EDGE EXHAUST FAN 3) CONDUCTORS FOR HP.1 NOT SIZED FOR FUSE AMPACITY |
|
| 02/12/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |