Permit: T09CM00443

Parcel: 133420570

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/04/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
02/02/2010 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) SEAL AROUND CONDUITS ADN CONDENSATE DRAINS AT ROOF PENETRATION
2) UNIT MISSING ROOF JACK AT CONDENSATE PENETRATION
3) PROVIDE A SCREEN IN EXHAUST T-TOP UNIT C
4) FINISH CONDENSATE CONNECTION TO UNIT D
5) ID DRYER VENT T-TOPS AND REMOVE SCREEN AS NECESSARY
6) 2 UNITS DATA PLATES NOT MARKED CORRECTLY FOR HEAT STRIPS
01/20/2010 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONDENSATE HOSE CONNECTIONS TO LAVS ARE KINKED
2) UNITS NOT IN PLACE YET
3) OK FOR TEP CLEARANCE