Permit: T09CM00443

Parcel: 133420570

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
02/10/2010 PLUMBING - FINAL Approved IVRS - Inspection :*
02/05/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) OK TO COVER DRAIN LINE IN WALL
02/04/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) UNIT D WATER HEATER REQUIRES A DRAIN PAN WITH DRAIN TO EXTERIOR
2) AAV MISSING AT UNIT C KS
3) PROVIDE BACKLOW CERTS, ENERGIZE ALL WATER HEATERS
4) VENT TERMINATIONS
02/02/2010 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) WATER HAMMER ARRESTORS ARE REQUIRED AT WB
2) SOLID CLEANOUT PL;UGS ARE NOT LISTED FOR A WOOD SCREW
3) EXPOSE UPSTREAM, BELOW GRADE CONNECTION AT PUB. INSTALL A UNION
4) PLASTIC CABLE TILES ARE NOT LISTED OR ACCEPTABLE TO SUPPORT DW DRAIN
5) SANITARY TEES ARE NOT LISTED FOR HORIZONTAL DRAINAGE
6) PROVIDE INSTALLATION INSTRUCTIONS FOR AAV
7) ALL THREADED CONNECTIONS TO WASTE AND VENT SYSTEMS REQUIRE APPROVED THREAD SEALANT
8) VENT TERMINATIONS REQUIRED TO BE 1 FOOT AWAY OR 6" ABOVE ANY SIDE WALL ORBSTRUCTIONS AND PAINT FOR UV PROTECTION
9) COINTINUED DENIALS MAY RESULT IN REFEES
01/21/2010 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PVB REQUIRES A UNION FOR SERVICING, ALSO NEED TO SEE CONN TO COPPER BELOW GRADE AND CERT TEST
2) SEAL THREADS ON CLEANOUT PLUGS, REPLACE DAMAGED PLUGS WITH PLUGS LISTED TO RECEIVE A SCREW
3) DW REQUIRES A SEPERATE SHUT OFF VALVE
4) AAV INSTALLATION INSTRUCTIONS REQUIRE IT TO BE INSTALLED AS HIGH AS POSSIBLE WHILE STILL ALLOWING CLEARANCE
5) TRAP ARM MAY HAVE ONLY ONE SLIP NUT
6) SECURE DW HOSE WITH AN APPROVED CLAMP
7) P-TRAP INSTALLED BACKWARDS
8) LABEL ELECTRICAL PANEL FOR NON METALLIC PIPING
9) PROVIDE ROOF ACCESS
10) INSPECTED UNIT "A" ONLY