Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2010 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 01/20/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) BLDG AND SERVICE OK-READY FOR POWER |
|
| 12/21/2009 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 12/18/2009 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDS AND NEUTRALS AT HOUSE PANEL TO BE SEPERATE 2) SEAL OPENINGS AT BACK OF PANEL WHERE WIRES ENTER WITH NON COMBUSTIBLE MATERIAL 3) UNITS TO BE SWITCHED AND PLUGGED 8' AND DOWN BEFORE POWER CAN BE RELEASED 4) NEED TO POST BOND WITH CITY TO GET POWER RELEASED 5) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT NEUTRAL BAR 6) BOND METALLIC PIPING SYSTEMS TO SERVICE 7) FINISH PANEL MAKE UP IN UNITS |