Permit: T09CM00308

Parcel: 140430130

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
04/12/2010 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) DUCT ABOVE SUSPENDED CEILING OK TO COVER
04/07/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE MIN. 2" BEADED COLLARS ON ALL FLEX DUCT CONNECTIONS PER MANUFACTURERS INSTALLATION INSTRUCTIONS
2. ABOVE CEILING CONNECTIONS NOT COMPLETE
3. ALL BRANCH DUCT TAKE-OFF'S TO BE PER DETAIL 4/MS.1
4-M5.1
03/30/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) GAS CARD LEFT WITH G.C. WITH G.C. AGREEING NOT TO FIRE OR START UP A/C 4 UNTIL NEW HOOD OVER O.S.A. IS INSTALLED
03/02/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
02/09/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE CLEARANCE TO OSA INLETS FROM FLUE DISCHARGE
02/02/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WALKED JOB SITE FOUND NEITHER THE GENERAL CONTRACTOR OR THE HVAC CONTRACTOR TO BE ON SITE 10:00 AM
12/07/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TO PROCEED
08/25/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) UNDERGROUND DUCT OK TO COVER (GF-4)