Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00308
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2010 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) INNER CHAMBER SCOPE BY RAYTHEON 2) ELECTRICAL BY OTHERS |
|
09/09/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* FIRE PUMP: 1) FILL UNUSED OPENINGS 2) RACEWAYS TO BE PER 695.14 (E) A/C AREA: 1) BONDING PER 250.97 2) RECEPT COVERS TO BE PER 406.8 3) WILL NEED COPY OF GENERATOR TEST REPORT 4) FINISH CHAMBER TO INSPECT |
|
08/25/2010 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCES AND SPACE FOR DISCONNECTING MEANS 2) ONLY ONE CONDUCTOR TO LUG CONNECTIONS 3) PROTECT CONDUCTORS 300.4 4) FILL UNUSED OPENINGS IN BOXES 5) CANNOT MODIFY CAS BOXES USE ONLY HOLE BY MANUFACTURE WITH THREADS 6) PLEASE VERIFY LISTING AND LABELING OF EQUIPMENT |
|
04/30/2010 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK LIGHTS ON HIGHEST CEILING |