Permit: T09CM00308

Parcel: 140430130

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T09CM00308

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2010 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
11/23/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
11/20/2009 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) PROTECT CONDUCTOR 13.8 KVA TO 480 VA, 252.46 AND 300.4
2) PROVIDE ILLUMINATION AT EQUIPMENT 110.26 (D)
3) BOND LINE SIDE RACEWAYS 250.102 AND 250.66
4) PHASE CONDUCTORS WITH COVER PER 210.5 (C) ?
5) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT
6) OK 13.8 KVA CONNECTIONS AND PULL BOXES