Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T09CM00308
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2010 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
11/23/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
11/20/2009 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUCTOR 13.8 KVA TO 480 VA, 252.46 AND 300.4 2) PROVIDE ILLUMINATION AT EQUIPMENT 110.26 (D) 3) BOND LINE SIDE RACEWAYS 250.102 AND 250.66 4) PHASE CONDUCTORS WITH COVER PER 210.5 (C) ? 5) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT 6) OK 13.8 KVA CONNECTIONS AND PULL BOXES |