Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM00072
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
05/27/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES EVERYTHING WEST OF GRID LINE D |
|
05/18/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE LINED BOXES ON SUPPLY DIFFUSERS AND OBD's 2. PROVIDE RETURN GRILLES 3. PROVIDE A LETTER FROM THE ENGINEER IF CHANGING ANY DETAILS |
|
04/28/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CONDENSATE DRAINS INTERNALLY TRAPPED OK TO SHEETROCK IT ROOM OK TO PROCEED WITH GRID CEILINGS |